Product Catalogue
Home > Product Center - NNULJTIG->Residual current circuit breaker -> DZ30LE Earth Leakage Circuit Breaker with Over Current Protection
Number of Poles | 1P+N |
Rated Current (A) | 6, 10, 16, 20, 25, 32 |
Rated Residual Operating Current (IΔn)(mA) | 30 |
Rated Residual Non-operation Current (IΔno)(mA) | 15 |
Rated Voltage (V) | 230 |
Residual Current Off-time | ≤0.1S |
Short Circuit Capacity(lcu) | 4500A |
Testing Current(A) |
Rated Voltage(V) |
Limited Time |
Pre-engage Result |
Start Situation |
Note |
1.13In | all | t≥1h | non-trip | cold state |
The current rise steadily to a fixed value within 5s |
1.45In | all | t<1h | trip | heat state | |
2.55In | all | 1s<t<60s | trip | cole state |
Open the supplementary switch, connect the power |
5In | all | t≥0.1s | non-trip | cold state |
Open the supplementary switch, connect the power |
10In | all | t<0.1s | trip | cole state |
Open the supplementary switch, connect the power |